Non-AHRI Certified Equipment Challenge Test Results
The Challenge Tests of the following non-AHRI Certified models established that the
Manufacturer (AEROSYS) failed to meet their claimed ratings when tested in accordance with AHRI Standard 210/240. The Challenge Testing procedures outlined in AHRI’s Certification Program General Operations Manual were followed for the tests. The General OM can be found at www.ahrinet.org.
The claimed efficiency and
the test results are listed below.
|
Model Number:
|
THDC-30T
|
|
Coil Model Number:
|
FKDNF003
|
|
Cooling Capacity:
|
28600
|
|
SEER:
|
11.00
|
|
Date of Testing:
|
July 31, 2009
|
|
Cooling Capacity:
|
21600 *
|
|
SEER:
|
7.60 *
|
|
Model Number:
|
THDC-30TG
|
|
Coil Model Number:
|
FV4BNF005AAAA
|
|
Cooling Capacity:
|
28600
|
|
SEER:
|
11.00
|
|
Date of Testing:
|
August 11-12, 2009
|
|
Cooling Capacity:
|
19400 *
|
|
SEER:
|
8.65 *
|
* Failed to meet ratings claimed by the manufacturer
|
|